View Enquiry: BE 2014-3014-018


Contract Details
Contract Number
2014-3014
Region
West
Tender Owner
MTO Capital
Location
Highway 401 Reconstruction and Widening from 0.3 km East of Waterloo Regional Road 8 to 0.1 km West of Waterloo Regional Road 24
Highway
401
Length
5.5
QMS Declaration
Yes
Option A or B bidding
No
Contract Description
Grading, Drainage, Hot Mix Paving, Granular Base, Electrical, Structure Rehabilitation (3) and Structure Replacement (5)
Tender Instructions
Contract Dates
Tender Advertise
04-Feb-2015
Tender Opening
16-Apr-2015 at 03:00:00 PM
TRF Submission Opening
19-Mar-2015
TRF Submission Closing
10-Apr-2015 at 12:00:00 PM

Enquiry Details
Enquiry Date
23-Mar-2015 at 12:17:18 PM
Type
Contract Drawing
Subject
Electrical and Pipe Culvert
Enquiry
Question # 1- UPC 1 and 2 Book 3 Sheet # 179 - will need to go under the storm sewer at the median between the east and west bound 401 lanes. The concrete box culvert and Fountian St overpass concrete walls will also need clearance under them Plus/minus 3 meters will be needed under the 401. The alignment of UPC 1 and 2 will put the bore pit in the side slop of the Fountian St overpass the east side of the pits will be plus/minus 9 meters deep and the west side plus/minus 3 meters deep. Can this be staged with Fountian St Overpass Removal? Question # 2 - Item # 49 Book 2 Sheet # 86 Culvert # 2- 1600mm. Is steel casing acceptable? Is there a secondary liner?

Response Details
Response Status
Completed
Response Date
02-Apr-2015 at 07:50:13 AM
Response
Question # 1 - The UPC 1 and UPC 2 are to be completed in Stage 2A as indicated in the Contract Documents at which point the new Fountain Street Bridge will be finished providing additional space for installing the crossing. The bore portion of the installation is from edge of existing pavement to edge of existing pavement as noted on the Quantity Sheets and the remainder of the installation is open cut. Question # 2 - Steel Casing is acceptable provided the requirements as detailed in the Tunnel special provision are met. A secondary liner would be required depending on the tunnelling method selected by the Contractor as specified in the Tunnel Special Provision.